Trouble Shooting For Cooling Towers

TROUBLE SHOOTING FOR COOLING TOWERS 


#
Problem / Difficulty
Possible Causes
Remedies/Rectifying Action
1.
Excessive absorbed
current / electrical load
1. Voltage Reduction
Check the voltage
2 a. Incorrect angle of axial fan blades
Adjust the blade angle
2 b. Loose belts on centrifugal fans
 (or speed reducers)
Check belt tightness
3. Overloading owing to excessive air
flow-fill has minimum water loading per m2 of tower section
Regulate the water flow by means of the valve
4. Low ambient air temperature
The motor is cooled proportionately and hence delivers more than name plate power.

2.
Drift/carry-over of water outside the unit
1. Uneven operation of spray nozzles

Adjust the nozzle orientation and eliminate any dirt
2. Blockage of the fill pack
Eliminate any dirt in the top of the
fill
3. Defective or displaced droplet
eliminator
Replace or realign the eliminators
4. Excessive circulating water flow
 (possibly owing to too high
pumping head)

Adjust the water flow-rate by means of the regulating valves.
Check for absence of damage to
the fill

3.
Loss of water from

1. Float-valve not at correct level
basins/pans
Adjust the make-up valve
2. Lack of equalizing connections

Equalise the basins of towers
operating in parallel

4.
Lack of cooling and
hence increase in
temperatures owing to
increased temperature
range

1. Water flow below the design valve

Regulated the flow by means
of the valves
2. Irregular airflow or lack of air

Check the direction of rotation of the fans and/or belt tension (broken belt possible)
3a. Recycling of humid discharge air
Check the air descent velocity
3b. Intake of hot air from other sources
Install deflectors
4a. Blocked spray nozzles (or even blocked spray tubes)
Clean the nozzles and/or the tubes
5. Scaling of the fill pack
Clean or replace the material
(washing with inhibited aqueous
sulphuric acid is possible but long,
complex and expensive)

Courtesy: beeindia.gov.in



Hope you will find above details inline. If you have any query or need your cooling tower cleaning services please contact us for more help and support.

L K Chatuvedi
CEO - Wetpoint Aqua Equipments (P) Ltd
Manufacturer of all kind of Industrial Cooling Towers and Spares
Phone: +91-9302.214.784
Email: ceo@wetpointcoolingtowers.com











Friday, 9 March 2018

Savings on New Cooling Tower




As we are the leading manufacturer of Cooling Tower in central part of India. We observe few points that can be beneficial for any organization to make savings on Cooling Tower.

Cooling towers as prefabricated, have not been the choice in past. Now a days era, replacing an old cooling tower can offer various options that might have been neglected in past.

  • The savings on labor, over a 'field' erected unit is not new. However, the latest advancements in technology have helped level the ‘field’. New technology offered some advantages as less lead time and build time.
  • Latest designed cross flow cooling towers and advanced drift eliminators improves efficiency that plays a vital role. 
  • Materials used to build a cooling tower ensures the compact design and low weight units. Materials as Composites Reinforced Fiberglass (FRP) can be used to achieve it.
  • Cooling tower basins can also play a crucial part on construction type. Most of the time on-site construction requires a concrete basin as a foundation, while most factory assembled units have a self-contained basin.
  • Some new designs are also available without basin, however, that allow existing basin to be used when updating to a newer factory assembled cooling tower systems, thus results in additional savings.

  • Multiple cells can also be mounted even be mounted on an existing basin.

If you have any query or need your cooling tower cleaning services please contact us for more help and support.


L K Chatuvedi
CEO - Wetpoint Aqua Equipments (P) Ltd
Manufacturer of all kind of Industrial Cooling Towers and Spares
Phone: +91-9302.214.784
Email: ceo@wetpointcoolingtowers.com

Monday, 18 December 2017

The Wet Bulb Temperature



Wet bulb temperature is an important factor in performance of evaporative water cooling equipment.  It  is  a  controlling  factor  from  the  aspect  of  minimum  cold  water  temperature  to  which water can be cooled by the evaporative method. Thus, the wet bulb temperature of the air enter-
ing the cooling tower determines operating temperature levels throughout the plant, process, or system.  Theoretically,  a  cooling  tower  will  cool  water  to  the  entering  wet  bulb  temperature, when operating without a heat load. However, a thermal potential is required to reject heat, so
it  is  not  possible  to  cool  water  to  the  entering  air  wet  bulb  temperature,  when  a  heat  load  is applied. The approach obtained is a function of thermal conditions and tower capability.

Wetpoint recommends the initial selection of towers with respect to design wet bulb temperature must be made on the basis of conditions existing at the tower site. The temperature selected is generally close to the average maximum wet bulb for the summer months. An important aspect of wet bulb selection is, whether it is specified as ambient or inlet. The ambient wet bulb is the temperature, which exists generally in the cooling tower area, whereas inlet wet bulb is the wet bulb temperature of the air entering the tower.  The later can be, and often is, affected by discharge vapours being recirculated  into  the  tower.  Recirculation  raises  the  effective  wet  bulb  temperature  of  the  air entering the tower with corresponding increase in the cold water temperature.  Since there is no initial knowledge or control over the recirculation factor, the ambient wet bulb should be specified. The cooling tower supplier is required to furnish a tower of sufficient capability to absorb the effects of the increased wet bulb temperature peculiar to his own equipment.

It is very important to have the cold water temperature low enough to exchange heat or to condense  vapours  at  the  optimum  temperature  level.    By  evaluating  the  cost  and  size  of  heat exchangers versus the cost and size of the cooling tower, the quantity and temperature of the cooling tower water can be selected to get the maximum economy for the particular process.

The below table illustrates the effect of approach on the size and cost of a cooling tower. The towers included were sized to cool 4540m3/hr through a 16.67°C range at a 26.7°C design wet bulb. The overall width of all towers is 21.65 meters; the overall height, 15.25 meters, and the
pump head, 10.6 m approximately.


If you have any query or need your cooling tower cleaning services please contact us for more help and support.


L K Chatuvedi
CEO - Wetpoint Aqua Equipments (P) Ltd
Manufacturer of all kind of Industrial Cooling Towers and Spares
Phone: +91-9302.214.784
Email: ceo@wetpointcoolingtowers.com