TROUBLE SHOOTING FOR COOLING TOWERS
|
#
|
Problem / Difficulty
|
Possible Causes
|
Remedies/Rectifying Action
|
|
1.
|
Excessive absorbed
current / electrical load
|
1. Voltage Reduction
|
Check the voltage
|
|
2 a. Incorrect angle of axial fan
blades
|
Adjust the blade angle
|
||
|
2 b. Loose belts on centrifugal
fans
(or speed reducers)
|
Check belt tightness
|
||
|
3. Overloading owing to excessive
air
flow-fill has minimum water loading
per m2 of tower section
|
Regulate the water flow by means
of the valve
|
||
|
4. Low ambient air temperature
|
The motor is cooled proportionately
and hence delivers more than name plate power.
|
||
|
2.
|
Drift/carry-over of water outside
the unit
|
1. Uneven operation of spray
nozzles
|
Adjust the nozzle orientation and eliminate
any dirt
|
|
2. Blockage of the fill pack
|
Eliminate any dirt in the top of
the
fill
|
||
|
3. Defective or displaced droplet
eliminator
|
Replace or realign the eliminators
|
||
|
4. Excessive circulating water
flow
(possibly owing to too high
pumping head)
|
Adjust the water flow-rate by means
of the regulating valves.
Check for absence of damage to
the fill
|
||
|
3.
|
Loss of water from
|
1. Float-valve not at correct
level
basins/pans
|
Adjust the make-up valve
|
|
2. Lack of equalizing connections
|
Equalise the basins of towers
operating in parallel
|
||
|
4.
|
Lack of cooling and
hence increase in
temperatures owing to
increased temperature
range
|
1. Water flow below the design
valve
|
Regulated the flow by means
of the valves
|
|
2. Irregular airflow or lack of
air
|
Check the direction of rotation of the
fans and/or belt tension (broken belt possible)
|
||
|
3a. Recycling of humid discharge air
|
Check the air descent velocity
|
||
|
3b. Intake of hot air from other sources
|
Install deflectors
|
||
|
4a. Blocked spray nozzles (or even blocked spray tubes)
|
Clean the nozzles and/or the tubes
|
||
|
5. Scaling of the fill pack
|
Clean or replace the material
(washing with inhibited aqueous
sulphuric acid is possible but
long,
complex and expensive)
|
Courtesy: beeindia.gov.in
Hope you will find above details inline. If you have any query or need your cooling tower cleaning services please contact us for more help and support.
L K Chatuvedi
CEO - Wetpoint Aqua Equipments (P) Ltd
Manufacturer of all kind of Industrial Cooling Towers and Spares
Phone: +91-9302.214.784
Email: ceo@wetpointcoolingtowers.com
CEO - Wetpoint Aqua Equipments (P) Ltd
Manufacturer of all kind of Industrial Cooling Towers and Spares
Phone: +91-9302.214.784
Email: ceo@wetpointcoolingtowers.com
No comments:
Post a Comment